1) A Proportional Controller is used for controlling temperature in melting
process. Temperature set point is750°C and temperature measuring
tool range is 0 - 1000°C . Proportional space is set at
15%. Pressure output range from controller is 20 –100 kN/m2 and
pressure output rises when temperature increases. If pressure output
is set at 60 kN/m2 for temperature set point, find
-7.5= 750 - Mv (100) 0 = 100 Ep + 50
1000 -0 15
100
Ep = -7.5
100 = 100 Ep + 50 Mv = -67500C #
15
100 Ep = 100- 50
Kp = 100
40
i) Temperature
for pressure output at 20 kN/m2
Pb = 15 % Kp = 100
Pb(0) = 50% 50
P = 20kN/m2
Kp = 100
15
E = Sp – Mv (100)
Range P(t) = KpEp + P(0)
Range P(t) = KpEp + P(0)
-7.5= 750 - Mv (100) 0 = 100 Ep + 50
1000 -0 15
Mv = 825 0 C 100Ep = 50
15
Ep =
50 (15)15
100
Ep = -7.5
ii) Temperature
for pressure output at 100kN/m2
P = 100 kN/m2 E= Sp
– Mv (100)
P =
100%
Range
Kp = 100 7.5 = 750 –Mv (100)
15 1000
Kp = 100 7.5 = 750 –Mv (100)
15 1000
P(t)
= KpEp + P(0) Mv
= (7.5 x 1000) - 750
100 = 100 Ep + 50 Mv = -67500C #
15
100 Ep = 100- 50
15
Ep= 50 (15)
100
Ep= 50 (15)
100
Ep = 7.5
2) In a process, a
Proportional Controller is used to control the liquid level in the boiler.
The
level is set at 8 meters and the level range is 1 to 14 meters. Proportional
band is at
20%. The output current has a range of 5 – 20mA. Determine:-
i. The output level when
current is 5 mA.
Ep = Sp – Mv ( 100 ) P(t) = KpEp + P(0)
range
Ep
= 8 – 10 x 100 P = 5(-15.38) + 50
14 – 1
Ep
= -15.38 p = -26.9 %
= current
– min. x 100
Max - min
-26.9 = Mv – 1 x 100
14 – 1
-26.9(13) = Mv – 1
100
100
Mv = - 2.5
ii. The output current at a
level of 10 meters.
controller output = current
– Min out x 100
max out – min out
= 10 – 5 x 100
20 – 5
20 – 5
= 5 x
20%
15
15
= 7 meters
3) An air to open valve on the inflow controls level in a tank. When the
process is at the set point the valve opening is 50%. An increase in
outflow results in the valve opening increasing to a new steady
state value of 80%. What is the resulting offset if the controller PB is:
i) 80%
Pb = 100
proportional gain, Kp
80 = 100
Kp
Kp = 100
80
Pb = 100
proportional gain, Kp
80 = 100
Kp
Kp = 100
80
ii) 40%.
Pb = 100
Proportional gain, Kp
40 = 100
Kp
Kp
40
4. A temperature controller has the
following characteristic curve below: